Please use this identifier to cite or link to this item: http://nopr.niscpr.res.in/handle/123456789/19396
Full metadata record
DC FieldValueLanguage
dc.contributor.authorThangavel, P.-
dc.contributor.authorSomasundaram, P.-
dc.date.accessioned2013-07-02T05:23:07Z-
dc.date.available2013-07-02T05:23:07Z-
dc.date.issued2013-07-
dc.identifier.issn0975-1084 (Online); 0022-4456 (Print)-
dc.identifier.urihttp://hdl.handle.net/123456789/19396-
dc.description454-460en_US
dc.description.abstractThe objective of this paper is to study the effect of evaporator load on performance of vapour compression refrigeration system with hydrocarbon refrigerants at different loads in evaporator. Hydrocarbon mixture (HCM) is an alternative refrigerant for hydro fluorocarbon (HFC) and chlorofluorocarbon (CFC) compounds due to their lower global warming potential (GWP) and zero ozone depletion potential (ODP). The impact on the environment is also reduced due usage of hydrocarbons as refrigerants. 50% of Propane (R290) and 50% of Isobutene (R600a) by mass fraction is used as a refrigerant in this analysis. Effects of condenser and evaporator temperature are computationally analysised. Various performance parameters like compressor input power, discharge temperature, heat rejected in the condenser, refrigeration effect and coefficient of performance are investigated at various loads of 25%, 50%, 75% and 100% in the evaporator. As compared to other loads, 75% load in the evaporator is economic mode to operate the system due to 3.81% reduction in compressor input power, 4.76 % reduction in discharge temperature, better condenser heat rejection rate and refrigeration effect.en_US
dc.language.isoen_USen_US
dc.publisherNISCAIR-CSIR, Indiaen_US
dc.rightsCC Attribution-Noncommercial-No Derivative Works 2.5 Indiaen_US
dc.sourceJSIR Vol.72(07) [July 2013]en_US
dc.subjectEvaporator loaden_US
dc.subjectR290en_US
dc.subjectR600aen_US
dc.subjectDischarge temperatureen_US
dc.subjectCompressor input poweren_US
dc.subjectRefrigeration effecten_US
dc.titlePart load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerantsen_US
dc.typeArticleen_US