Please use this identifier to cite or link to this item:
http://nopr.niscpr.res.in/handle/123456789/19396| Title: | Part load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerants |
| Authors: | Thangavel, P. Somasundaram, P. |
| Keywords: | Evaporator load;R290;R600a;Discharge temperature;Compressor input power;Refrigeration effect |
| Issue Date: | Jul-2013 |
| Publisher: | NISCAIR-CSIR, India |
| Abstract: | The objective of this paper is to study the effect of evaporator load on performance of vapour compression refrigeration system with hydrocarbon refrigerants at different loads in evaporator. Hydrocarbon mixture (HCM) is an alternative refrigerant for hydro fluorocarbon (HFC) and chlorofluorocarbon (CFC) compounds due to their lower global warming potential (GWP) and zero ozone depletion potential (ODP). The impact on the environment is also reduced due usage of hydrocarbons as refrigerants. 50% of Propane (R290) and 50% of Isobutene (R600a) by mass fraction is used as a refrigerant in this analysis. Effects of condenser and evaporator temperature are computationally analysised. Various performance parameters like compressor input power, discharge temperature, heat rejected in the condenser, refrigeration effect and coefficient of performance are investigated at various loads of 25%, 50%, 75% and 100% in the evaporator. As compared to other loads, 75% load in the evaporator is economic mode to operate the system due to 3.81% reduction in compressor input power, 4.76 % reduction in discharge temperature, better condenser heat rejection rate and refrigeration effect. |
| Page(s): | 454-460 |
| ISSN: | 0975-1084 (Online); 0022-4456 (Print) |
| Appears in Collections: | JSIR Vol.72(07) [July 2013] |
Files in This Item:
| File | Description | Size | Format | |
|---|---|---|---|---|
| JSIR 72(7) 454-460.pdf | 465.12 kB | Adobe PDF | View/Open |
Items in NOPR are protected by copyright, with all rights reserved, unless otherwise indicated.