Please use this identifier to cite or link to this item:
http://nopr.niscpr.res.in/handle/123456789/29786| Title: | Application of adsorption technique in the estimation of drift losses through the cooling towers |
| Authors: | Joshi, P V Bedekar, S D Nair, P V N War, S B Vyas, S B Saini, R P |
| Issue Date: | Jun-1996 |
| Publisher: | NISCAIR-CSIR, India |
| Abstract: | Adsorption technique has been used in the estimation of drift losses through the cooling towers of Central Air-conditioning Plant (CAP), BARC. CAP uses two types of drift eliminators for minimizing the drift losses. Using molecular sieves as adsorbent, the efficiency of eliminator I and eliminator II was estimated to be 80.12 and 99.25% respectively. The additional water saving due to the use of eliminator II instead of eliminator I is estimated to be 59.28 m3 per day. |
| Page(s): | 101-104 |
| ISSN: | 0975-1017 (Online); 0971-4588 (Print) |
| Appears in Collections: | IJEMS Vol.03(3) [June 1996] |