Title: Application of adsorption technique in the estimation of drift losses through the cooling towers
Authors: Joshi, P V
Bedekar, S D
Nair, P V N
War, S B
Vyas, S B
Saini, R P
Issue Date: Jun-1996
Publisher: NISCAIR-CSIR, India
Abstract: Adsorption technique has been used in the estimation of drift losses through the cooling towers of Central Air-conditioning Plant (CAP), BARC. CAP uses two types of drift eliminators for minimizing the drift losses. Using molecular sieves as adsorbent, the efficiency of eliminator I and eliminator II was estimated to be 80.12 and 99.25% respectively. The additional water saving due to the use of eliminator II instead of eliminator I is estimated to be 59.28 m3 per day.
Page(s): 101-104
ISSN: 0975-1017 (Online); 0971-4588 (Print)
Appears in Collections:IJEMS Vol.03(3) [June 1996]